AQS201 SETTINGS TO SATISFY ASHRAE 62.2 STD |
| BR |
AREA |
62.2 |
AC |
Total |
Input |
Run |
Wait |
Vent |
| # |
sq. ft. |
cfm |
tons |
cfm |
cfm |
min |
min |
cfm |
| 1 |
750 |
23 |
1.5 |
600 |
36 |
33 |
20 |
23 |
| 2 |
1000 |
33 |
2.0 |
800 |
48 |
42 |
20 |
33 |
| 2 |
1250 |
35 |
2.5 |
1000 |
60 |
28 |
20 |
35 |
| 2 |
1500 |
38 |
3.0 |
1200 |
72 |
22 |
20 |
38 |
| 3 |
1500 |
45 |
3.0 |
1200 |
72 |
33 |
20 |
45 |
| 2 |
1750 |
40 |
3.5 |
1400 |
84 |
18 |
20 |
40 |
| 3 |
1750 |
48 |
3.5 |
1400 |
84 |
26 |
20 |
48 |
| 4 |
1750 |
55 |
3.5 |
1400 |
84 |
38 |
20 |
55 |
| 3 |
2000 |
50 |
4.0 |
1600 |
96 |
22 |
20 |
50 |
| 4 |
2000 |
58 |
4.0 |
1600 |
96 |
30 |
20 |
58 |
| 5 |
2000 |
65 |
4.0 |
1600 |
96 |
42 |
20 |
65 |
| 3 |
2500 |
55 |
5.0 |
2000 |
120 |
17 |
20 |
55 |
| 4 |
2500 |
63 |
5.0 |
2000 |
120 |
22 |
20 |
63 |
| 5 |
2500 |
70 |
5.0 |
2000 |
120 |
28 |
20 |
70 |
| 6 |
2500 |
78 |
5.0 |
2000 |
120 |
36 |
20 |
78 |
|